Shopping List
Shopping List
AUD - AU$
Image
/
/
/
/
Schneider Electric A9A26927 Acti 9 -Auxiliary Fault Contact Isd - 1 C/O - AC/DC
Schneider Electric A9A26927 Acti 9 -Auxiliary Fault Contact Isd - 1 C/O - AC/DC
Image
Image
Technical Data Sheets
Product Description

Schneider Electric A9A26927 Acti 9 -Auxiliary Fault Contact Isd - 1 C/O - AC/DC

This Acti9 iSD electric auxiliary is a remote fault indicator contact. It is dedicated to iC60, iC40, iCV40, iID, iID40, iDPN Vigi, iSW-NA, iC60 & iID products. It comes with 1 changeover contact indicating the position of the associated device. It indicates the position of the associated device in the event of electrical fault or action on the tripping auxiliary. There is a mechanical state indicator and a test function button on the front face.

The Ue rated operational voltage is 24VAC to 415VAC or 24VDC to 130VDC. The operating frequency is 50Hz or 60Hz. The Ie rated operational current is 6A under 24VDC, 2A under 48VDC, 1.5A under 60VDC, 1A under 130VDC. The Ie rated operational current is 6A under 24VAC to 240VAC, 3A under 415VAC. The width in 9mm pitches is 1.

The product color is white (RAL9003). The dimensions are (W) 9mm x (H) 86mm x (D) 73mm. Product weight is 33g. The degree of protection is IP20 at terminals and IP40 in enclosure. The operating temperature is -35°C to +70°C. The storage temperature is -40°C to +85°C. This product complies with EN/IEC 60947-5-1 standard.


AU $ 71.20
Quantity:
/ EA
This item is sold by
Image
MY-2155714050
Shop by Specification Table
You can find items with similar specifications from the table below.
Auxiliary Contact
18 Items
auxiliary-contact-img
Rated Current
6 A at 120 V AC-15 1.04 A at 690 V AC-15 0.55 A at 125 V DC-13 0.1 A at 600 V DC-13, 6 A at 120 V AC-15 3 A at 240 V AC-15 1.8 A at 400 V AC-15 1.5 A at 480 V AC-15 2.8 A at 24 V DC-13 1.4 A at 48 V DC-13 0.55 A at 125 V DC-13 0.27 A at 250 V DC-13 0.15 A at 400 V DC-13, AC-12: 3 A at 250 V AC 50/60 Hz AC-12: 5 A at 125 V AC 50/60 Hz AC-12: 5 A at 24 V AC 50/60 Hz AC-12: 5 A at 48 V AC 50/60 Hz AC-15: 2 A at 250 V AC 50/60 Hz AC-15: 3 A at 125 V AC 50/60 Hz AC-15: 5 A at 24 V AC 50/60 Hz AC-15: 5 A at 48 V AC 50/60 Hz DC-12: 0.2 A at 250 V DC DC-12: 0.4 A at 125 V DC DC-12: 2.5 A at 48 V DC DC-12: 4 A at 24 V DC DC-14: 0.2 A at 250 V DC DC-14: 0.4 A at 125 V DC DC-14: 1 A at 48 V DC DC-14: 3 A at 24 V DC, AC-12 3 A at 380...415 V, AC 50/60 Hz AC-12 6 A at 220...240 V, AC 50/60 Hz DC-12 1 A at 130 V, DC DC-12 1.5 A at 60 V, DC DC-12 2 A at 48 V, DC DC-12 6 A at 24 V, DC
Colour
Dark grey, White
Range
Acti9, EasyPact, TeSys, TeSys TeSys Deca
Standard
EN/IEC 60947-5-1, EN/IEC 60947-5-1 GB/T 14048.5, EN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.5, EN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.5 JIS C8201-5-1
[Ui] Rated Insulation Voltage
400 V, 500 V, 690 V conforming to IEC 60947-1 300 V conforming to UL 508 300 V conforming to CSA C22.2 No 14, 690 V conforming to IEC 60947-5-1 600 V conforming to UL 600 V conforming to CSA
IP Degree of Protection
IP20 conforming to EN/IEC 60947-5-1, IP20 conforming to IEC 60529, IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Ambient Air Temperature for Operation
-20…50 °C, -25…50 °C, -25…60 °C, -35…70 °C
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Auxiliary Contact from SCHNEIDER ELECTRIC
Source & compare similar products
More from Auxiliary Contact
Expand your search with a wider selection
Recently Viewed Products
Compare & Refer to previously viewed items
Image
Top
Image