range
TeSys
product or component type
Contactor coil
device short name
LX1D6
control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
220 V AC 50/60 Hz
average resistance
102 Ohm at 20 °C
inductance of closed circuit
6.7 H
product compatibility
LC1D80 LC1D95
mechanical durability
4 Mcycles
maximum operating rate
3600 cyc/h 60 °C
Complementarycoil technology
Without built-in suppressor module
control circuit voltage limits
Drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C) Operational: 0.8...1.1 Uc at 50 Hz (at <55 °C) Operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)
inrush power in VA
245 VA 60 Hz cos phi 0.75 (at 20 °C) 245 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA
26 VA 60 Hz cos phi 0.3 (at 20 °C) 26 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation
6…10 W at 50/60 Hz
Environmentambient air temperature for operation
-5…60 °C
net weight
0.28 kg