4300 is simplified earth resistance tester (based on 2-pole method) that can be used for various distribution lines and electrical appliances and it also can measure AC/DC voltage. (As for AC Voltages, true rms values can be obtained.)
• 200/2000Ω (2 ranges): auto-ranging.
• Warning buzzer triggered at 100Ω or less.
• LED lights up when a large earth voltage is detected.
• Live circuit warning when 30V or higher voltage is detected. (KEW 4300 detects voltage even when measuring resistances.)
• LED light for illuminating measurement points.
(It turns on/off automatically in relation to the ambient brightness.)
• Small test current (max 2mA) not triggering RCD.
EARTH RESISTANCE RANGES 200.0/2000Ω (Auto ranging) ±3%rdg±5dgt
VOLTAGE RANGES
AC: 5.0 – 300.0V (45 – 65Hz)±1%rdg±4dgt
DC: ±5.0 – 300.0V±1%rdg±8dgt
APPLICABLE STANDARDS
IEC 61010-1 CAT III 300V pollution degree 2
IEC 61010-031, 61557-1, -5
IEC 61326-1, 2-2, IEC 60529 (IP40)
POWER SOURCE LR6(AA)(1.5V) × 2pcs
DIMENSIONS 232(L) × 51(W) × 42(D)mm
WEIGHT 220g approx. (including battery)
INCLUDED ACCESSORIES
7248 (Test lead with Alligator clip and Flat test probe)
8072 (CAT II Standard prod)
8253 (CAT III Standard prod)
8017 (Extension prod long)
9161 (Carrying case)
Instruction manual, LR6 (AA) × 2