TeSys GV electrical trip, MN undervoltage release, 220-240V AC 60Hz, for motor circuit breakers GV2, GV3. It trips the circuit breaker when the control voltage drops below 0.35 Uc, possible opening between 0.35-0.7 Uc. Closing of the circuit breaker is only possible when the control voltage is applied in the range 0.85-1.1 Uc. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Specifications:
Range:
Product or Component Type:
Device Short Name:
Complementary:
- Range Compatibility:
- TeSys GV2ME
- TeSys GV2LE
- TeSys GV2L
- TeSys GV2P
- TeSys GV3L
- TeSys GV3P
- TeSys Deca
- [Uc] Control Circuit Voltage:
- Control Circuit Voltage Limits:
- [Ui] Rated Insulation Voltage:
- 690 V AC (IEC 60947-1)
- 600 V AC (UL 60947-4-1)
- 600 V AC (CSA C22.2 No 60947-4-1)
- Threshold Tripping Voltage:
- Inrush Power:
- Hold-in Power Consumption:
- Operating Time:
- On-load Factor:
- Connections - Terminals:
- Screw Clamp Terminals:
- 1 cable(s) 1…2.5 mm² solid
- 2 cable(s) 1…2.5 mm² solid
- 1 cable(s) 0.75…2.5 mm² flexible without cable end
- 2 cable(s) 0.75…2.5 mm² flexible without cable end
- 1 cable(s) 0.75…1.5 mm² flexible with cable end
- 2 cable(s) 0.75…1.5 mm² flexible with cable end
- Tightening Torque:
- < 1.4 N.m on screw clamp terminals
- Mechanical Durability:
- 10,000 cycles with GV3P and GV3L
- 30,000 cycles with GV2ME and GV2P
- Quantity per Set:
- Dimensions:
- Height: 89 mm
- Width: 18 mm
- Depth: 66 mm
- Net Weight:
- Colour: