Range of product: Easy9
Product or component type: Residual current circuit breaker (RCCB)
Device short name: Easy9 RCCB
Poles: 2P
Neutral position: Left
[In] rated current: 63 A
Network type: AC
Earth-leakage sensitivity: 100 mA
Earth-leakage protection time delay: Instantaneous
Earth-leakage protection class: Type AC
Rated breaking and making capacity: 500 A
Rated conditional short-circuit current: Easy9 MCB: 6000 A 63 A
Complementary:
- Device location in system: Outgoer
- Network frequency: 50/60 Hz
- [Ue] rated operational voltage: 230 V AC 50/60 Hz
- Residual current tripping technology: Voltage independent
- [Ui] rated insulation voltage: 440 V AC
- [Uimp] rated impulse withstand voltage: 4 kV
- Surge current: 250 A
- Contact position indicator: Yes
- Control type: Toggle
- Mounting mode: Clip-on
- Mounting support: DIN rail
- Comb busbar and distribution block compatibility: Top: YES
- Connection pitch: 18 mm between phases, 9 mm pitches
- Height: 82 mm
- Width: 36 mm
- Depth: 72 mm
- Colour: Grey (RAL 7035)
- Mechanical durability: 5000 cycles
- Electrical durability: AC: 2000 cycles 230 V AC 50/60 Hz
- Connections - terminals: Tunnel type terminal (top or bottom) 1…35 mm² rigid, 1…25 mm² flexible
- Tightening torque: 3.5 N.m top or bottom
Environment:
- Standards: IEC 61008-1
- Product certifications: CE
- IP degree of protection: IP20
- Pollution degree: 2 conforming to IEC 61008-1
- Tropicalisation: 2
- Relative humidity: 95 % at 55 °C
- Ambient air temperature for operation: -5…60 °C
- Ambient air temperature for storage: -40…85 °C