• Large transformer jaws of 68mm diameter makes it possible to clamp on all three or four wires (3 phases) together for leakage current measurement.
• True RMS enables an accurate measurement for distorted waveforms.
• Measurement from mA up to AC 1000A
• Frequency filter switch to eliminate the effect of the harmonics.
• 2 way analogue output terminal
• Resolution 0.1mA
AC A
(50/60HZ) 200mA/2/20/200/1000A
±2.5%rdg±5dgt (200mA/2/20A)
±3.0%rdg±5dgt (200A, 0 – 500A)
±5.5%rdg (501 – 1000A)
AC A (WIDE)
200mA/2/20/200/1000A
±1.8%rdg±5dgt (50/60Hz) (200mA/2/20A)
±2.0%rdg±5dgt (50/60Hz) (200A, 0 – 500A)
±5.0%rdg (50/60Hz) (501 – 1000A)
CREST FACTOR
3.0 or less
CONDUCTOR SIZE
Ø68mm max.
FREQUENCY RESPONSE
40Hz – 1kHz
OUTPUT
Waveform :
AC200mV against the maximum value of each range (1000A range is 100mV)
Recorder :
DC200mV against the maximum value of each range (1000A range is 100mV)
APPLICABLE STANDARDS
IEC 61010-1 CAT III 300V Pollution degree 2
IEC 61010-2-032
POWER SOURCE
6F22 (9V) × 1 *Continuous measuring time: Approx. 60 hours
DIMENSIONS
250(L) × 130(W) × 50(D)mm
WEIGHT
Approx. 570g (including battery)
INCLUDED ACCESSORIES
9094 (Carrying Case)
6F22 × 1
Instruction Manual