- Test Voltage: 100V, 250V, 500V, 1000V (max 1000V)
- Measuring Ranges:
- 2.000/20.00/200.0MΩ (Auto-ranging)
- 20.00/200.0/1000MΩ (Auto-ranging)
- 20.00/200.0/2000MΩ (Auto-ranging)
- Accuracy:
- ±2%rdg±6dgt (2.000/20.00MΩ)
- ±5%rdg±6dgt (200.0MΩ)
- Rated Current:
- 1.0-1.2mA @ 0.1MΩ
- 1.0-1.2mA @ 0.25MΩ
- 1.0-1.2mA @ 0.5MΩ
- 1.0-1.2mA @ 1MΩ
- Short Circuit Current: 1.5mA max
Loop Impedance Function
- Types:
- LOOP ATT (L-PE/L-N 3-wire)
- LOOP HIGH (L-PE 2-wire)
- L-PE (0.01Ω Res)
- L-PE (0.001Ω Res)
- High Test Current (25A): L-N/L-L
- Rated Voltage: 100-260V (50/60Hz)
PSC/PFC (Prospective Short Circuit/Prospective Fault Current)
- Range: 2000A/20kA Auto-Ranging
- Accuracy: Derived from measured loop impedance specification and measured voltage specification
RCD Test
- Rated Voltage: 100-260V (50/60Hz)
- Functions: × 1/2, × 1, × 5, Ramp, Auto, Uc
- Trip Current Settings: Various settings for different RCD types
- Accuracy:
- Trip Current × 1/2: -8% to -2%, +2% to +8%
- Trip Current × 1: -10% to 0%, 0% to +10%
- Trip Current × 5: ±2% to ±8%
Continuity
- Range: 20.00/200.0/2000Ω (Auto-ranging)
- Open Circuit Voltage (DC): 7-14V
- Measuring Current: 200mA (200mA or more for 2Ω or less)
- Accuracy: ±2%rdg±8dgt
Volts
- Range: 300.0/600V (Auto-ranging)
- Measuring Ranges: 2-600V
- Frequency Range: 45-65Hz
- Accuracy: ±2%rdg±4dgt (Volts), ±0.5%rdg±2dgt (Frequency)
Phase Rotation
- Rated Voltage: 48-600V (45-65Hz)
- Display: Correct and reversed phase sequences indicated
Earth
- Range: 20.00/200.0/2000Ω (Auto-ranging)
- Accuracy:
- 20.00Ω: ±2%rdg±0.08Ω
- 200.0/2000Ω: ±2%rdg±3dgt
- Applicable Standards: IEC 61010-1 CAT IV 300V / CAT III 600V Pollution degree 2, IEC 61010-2-034, IEC 61557-1,2,3,4,5,6,7,10, IEC 60529 (IP40), IEC 61326 (EMC)
General
- Power Source: LR6 (AA) (1.5V) × 8
- Communication Interface: USB
- Dimensions / Weight: 136(L) × 235(W) × 114(D) mm / 1350g (including batteries)
Accessories
- Mains test lead, 7281 (Test leads with remote control switch), 7246 (Distribution board test lead), 7228A (Earth resistance test leads), 8041 (Auxiliary earth spikes [2 spikes/1 set]), 9084 (Soft case), 9142 (Carrying case), 9151 (Shoulder strap), 9199 (Shoulder pad), 8212-USB (USB adapter), LR6(AA) × 8, Instruction manual, Calibration certificate