Range
Acti9
Poles Description
1P
Network Type
AC
Number of Protected Poles
1
[In] Rated Current
125 A at 30 °C
Curve Code
C
Breaking Capacity
3 kA Icu at 380...415 V AC 50/60 Hz IT conforming to EN/IEC 60947-2 20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12 V DC conforming to EN/IEC 60947-2 15 kA Icu at 125 V DC conforming to EN/IEC 60947-2 10 kA Icu at <= 144 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Standards
EN/IEC 60898-1 EN/IEC 60947-2
Magnetic Tripping Limit
5...10 x In
Connection - Terminals
Tunnel type terminals1…50 mm² rigid Tunnel type terminals1.5…35 mm² flexible
IP Degree of Protection
IP20 conforming to IEC 60529
Ambient Air Temperature for Operation
-25…70 °C
Mechanical Durability
20000 cycles
Ambient Air Temperature for Storage
-40…85 °C
Electrical Durability
5000 cycles conforming to IEC 60947-2
Tightening Torque
3.5 N.m
Colour
White
This spec is not available in the specification table.
Width
27 mm
This spec is not available in the specification table.
Trip Unit Technology
Thermal-magnetic
This spec is not available in the specification table.
Control Type
Toggle
This spec is not available in the specification table.
Device Short Name
C120N
This spec is not available in the specification table.
Product Name
C120
This spec is not available in the specification table.
Range of Product
C120
This spec is not available in the specification table.
Depth
73 mm
This spec is not available in the specification table.
Device Application
Distribution
This spec is not available in the specification table.
Mounting Mode
Clip-on
This spec is not available in the specification table.
Network Frequency
50/60 Hz
This spec is not available in the specification table.
Suitability for Isolation
Yes conforming to IEC 60947-2
This spec is not available in the specification table.
[Ics] Rated Service Breaking Capacity
15 kA 75 % conforming to EN/IEC 60947-2 - 130 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC 2.25 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - <= 144 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 12 V AC 50/60 Hz 7500 A 75 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz
This spec is not available in the specification table.
Limitation Class
3 conforming to EN/IEC 60947-2
This spec is not available in the specification table.
[Ui] Rated Insulation Voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
This spec is not available in the specification table.
[Uimp] Rated Impulse Withstand Voltage
6 kV conforming to EN/IEC 60947-2
This spec is not available in the specification table.
Contact Position Indicator
Yes
This spec is not available in the specification table.
Mounting Support
35 mm symmetrical DIN rail
This spec is not available in the specification table.
Local Signalling
ON/OFF indication
This spec is not available in the specification table.
Overvoltage Category
IV
This spec is not available in the specification table.
Comb Busbar and Distribution Block Compatibility
YES
This spec is not available in the specification table.
9 mm Pitches
3
This spec is not available in the specification table.
Height
81 mm
This spec is not available in the specification table.
Pollution Degree
3 conforming to IEC 60947-2
This spec is not available in the specification table.
Relative Humidity
95 % at 55 °C
This spec is not available in the specification table.
Operating Altitude
2000 m
This spec is not available in the specification table.
Wire Stripping Length
15 mm
This spec is not available in the specification table.
Earth-Leakage Protection
Without
This spec is not available in the specification table.
[Ue] Rated Operational Voltage
380...415 V AC 50/60 Hz 125 V DC <= 144 V DC 12 V DC 220...240 V AC 50/60 Hz 230...400 V AC 50/60 Hz 130 V AC 50/60 Hz 12 V AC 50/60 Hz
This spec is not available in the specification table.
Product certifications
EAC
This spec is not available in the specification table.
Locking Options Description
Handle sealable with cable diameter 0.7mm in OFF or ON position
This spec is not available in the specification table.
Tropicalisation
2 conforming to IEC 60068-1
This spec is not available in the specification table.
Deskripsi Produk

Pemutus Sirkuit Miniatur Schneider Electric A9N18359 (mcb), Acti9 C120N, 1P, 125A, Kurva C, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Acti9 C120N ini merupakan miniatur pemutus sirkuit (MCB) multistandar tegangan rendah. Ini adalah pemutus sirkuit 1P dengan 1 kutub terlindung, arus pengenal 125A dan kurva tripping C. Kapasitas pemutusan hubung singkat terukur Icu hingga 3kA pada 380VAC hingga 415VAC sesuai dengan standar IEC/EN 60947-2. Produk ini mematuhi standar industri IEC/EN 60898-1 dan standar perumahan IEC/EN 60947-2. Pemutus sirkuit mini ini menggabungkan fungsi perlindungan sirkuit terhadap arus pendek dan beban berlebih, kontrol dan isolasi. Kehadiran jalur hijau menjamin kontak terbuka secara fisik dan memungkinkan pekerjaan dilakukan dengan aman di sirkuit hilir. Ini memiliki kapasitas menahan tegangan lebih yang baik. Produk ini dirancang untuk menawarkan tingkat kinerja industri yang tinggi. Produk ini memiliki ketahanan listrik hingga 5.000 siklus dan ketahanan mekanis hingga 20.000 siklus. Tegangan operasional Ue berubah dari 380VAC ke 415VAC. Tegangan insulasi pengenal Ui adalah 500VAC. Keterbatasannya kelas 3 (menurut standar IEC/EN 60947-2) meningkatkan biaya perlindungan sirkuit hilir. Produk dapat dijepitkan pada rel DIN. Lebarnya adalah 3 pitch 9mm. Tingkat polusi adalah 3. Kategori tegangan lebih adalah IV. Warna produk putih (RAL 9003). Dimensinya adalah (L) 27mm x (T) 81mm x (D) 73mm. Beratnya 0,205kg. Ia memiliki tingkat perlindungan IP20 (sesuai standar IEC 60529) pada terminalnya. Suhu pengoperasian dari -25°C hingga +70°C. Suhu penyimpanan dari -40°C hingga +85°C.

Rp 1.086.800
Kuantitas:
/ EA
This item is sold by
Image
MY-1270830467
Shop by Specification Table
You can find items with similar specifications from the table below.
Miniature Circuit Breakers - MCBs
181 Items
miniature-circuit-breakers-mcbs-img
Range
Acti9, Acti 9, Multi 9, TeSys
Poles Description
1P, 2P, 3P, 4P
Network Type
AC, AC DC, DC, DC AC
Number of Protected Poles
1, 2, 3, 4
[In] Rated Current
100 A at 30 °C, 10 A, 10 A at 25 °C, 125 A, 125 A at 30 °C
Curve Code
B, C, D
Breaking Capacity
10000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2, 10000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 375 V DC conforming to EN/IEC 60947-2, 10000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2, 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Miniature Circuit Breakers - MCBs dari SCHNEIDER ELECTRIC
Temukan dan bandingkan barang serupa
Lebih Dari Miniature Circuit Breakers - MCBs
Perluas pencarian anda dengan pilihan yang lebih bervariasi
Baru Saja Dilihat Produk
Bandingkan dan Rujuk ke item yang dilihat sebelumnya
Image
Atas
Image